Construction | 3/3-way with rotating spoolClosed loop control circuit and metal to metal seal |
Power supply | 24 V DC +/- 10%, max absorption 1.5 A |
Controlinput signal | 0-10 V (on request 4...20 mA or +/- 10 V DC) |
Command method | If the command signal is lower than 50%, the valve establishes a linkbetween inlet 1 with outlet 2. If the setpoint value is higher than 50%, theport 2 is connected with the exhaust 3. |
Hysteresis Linearity | LRWD2 = 1% / 1% FSLRPD2 = 0,2% / 0,3% FS |
Response time | ~ 5 ms |
Operating temperature | 0 ÷ 50°C |
Mounting position | In any positionN.B.: The optimal distance of the servo valve from the controlledvolume should not exceed 2m. Longer distances will lower the controlperformance. |
Fluid | Filtered air 5 μm, non-aggressive gases |
Relative air humidity | Max 90% |
Supply pressure | -0.9 ÷ 10 bar |
Leakage | < 1% of max flow rate |
Electrical connection | M12 connector, 8 pin, male |
Supplier code | DN ([mm]) | Max. flow-rate (6 Bar ΔP 1 Bar) ([Nl/min]) |
---|---|---|
label LRWD2-36-2-A-00 | 6 | 950 |
label LRWD2-34-2-A-00 | 4 | 690 |